After removing the router cover, three jumpers are accessible on a 6-pin jumper
block located near the EIA-485 connector. These impart 604 of bias via the upper
jumper (pull-up) and the lower jumper (pull-down), and 130 of termination
impedance with the middle jumper. With all three jumpers in place, the effective
termination resistance is 120 consistent with the MS/TP standard. If the
router is not installed at the end of a segment, remove all the jumpers and install
120 at each far end of the bus.
Figure 10 Internal Termination and Bias