TD100700-0MB
34
5.2.2 Universal Input — Configured as Binary Input
(Channels UI1–UI8)
You can accept a binary input with any channel UI1–UI8 as follows:
On the Main Page (Figure 13), click a title link from among UI1–UI8.
Under BAS Channel Configuration in the new page that appears (Figure 20),
set the Channel Type to Binary Input.
In the BACnet Object Configuration (lower) section of the screen, all items
are as described in Section 5.2 above — but Units defaults to NO_UNITS.
Attach your device to the pair of BASC20 pins for the chosen channel — so
that the more positive connection is to pin A and the more negative to pin C.
Figure 20 — Universal Input Configured as Binary Input