TD071200-0IK
19
those passed by the router from BACnet/IP. The default value
usually provides good performance.
6.4.5 MS/TP Baud Rate (Default Value = 38400)
The baud rate of the MS/TP network can be 9600, 19200, 38400
or 76800 bps. All MS/TP devices on the same MS/TP network
must use the same baud rate. On power up, as the router polls
for other masters, autobauding devices adjust to its baud rate.
6.4.6 MS/TP Tolerance (Default Selection = Strict)
This setting determines the degree to which interoperability with
devices is successful. The Lenient option is less efficient for
traffic flow but optimises interoperability. A slight improvement
in performance will be realised by selecting the Strict setting.